For this series of products, the diesel engines will choose from industrial series, like Cummins DCEC C type, and CCEC P type.
With the specification of the pump required, Kaihua engineer will choose the right diesel engine. The engine and pump will be connected by coupling, with smart controller and high water temperature and low oil pressure protection for the diesel engine.
1. Specification of Fire Pump Genset | |
Genset Model | KH-125GF |
Prime Power(KW)/(HP) | 125/170 |
Rated Voltage (V) | 400/230 |
Rated Frequency(Hz) | 50 |
Power Factor(COSφ) | 0.8 |
Rated Speed | 1500rpm |
Dimensions(mm) ----- (L×W×H) | 2500×950×1450 |
Genset Weight(kg) | 1800 |
Base Fuel Tank Capacity (L) | 800 |
2. Specification of Engine | |
Engine Brand | Powered by Cummins |
Engine Model | 6BTAA5.9-G12 |
Prime Power(KW) | 140 |
Standby Power(KW) | 155 |
Number of Cylinders | 6 |
Rated Speed | 1500rpm |
Cylinder Arrangement | Vertical in-line |
Cycle | Four stroke |
Air intake System | Turbo-charged & air/air cooled |
Fuel System | PN type fuel pump |
Bore×Stroke (mm) | 102x 120 |
Displacement (L) | 5.9 |
Compression Ratio | 16.0:1 |
Governor Type | Electronic |
Cooling System | Forced Water Cooling Cycle |
Total lubrication System Capacity (L) | 24 |
Fuel Consumption at 100% Load(g/kwh) | 207 |
Starting Method | DC24V electrical starting |
3. Specification of Fire Pump | |
Pump Brand | Nanfang Pump |
Pump Model | NSC200-125-480 |
Inlet Diameter(mm) | 200 |
Outlet Diameter(mm) | 125 |
Impeller Diameter(mm) | 480 |
Flow of the Pump(GPM) | 1250 |
Lift of the Pump (m) | 90 |
Shaft Diameter(mm) | 45 |
Bearing Model | 6309SKF |
Maximum Permissible Pressure(Mpa) | 1.6 |
Seal Type | Packing Seal |
Material of Pump body | Cast Iron |
Material of Impeller | Cast Iron |
Material of Seal Ring | Cast Iron |
Material of Shaft | Stainless |
4.Specification of Control Module | |
The control panel is the one with automatic start function, and the controller uses LCD display, optional Chinese and English display interface with operation easy and reliable. It can be widelyused in all types of generator automatic control system for compact structure, advanced circuits, simple connections and high reliability. |
|
Protection functions: It will give alarm signals when the output parameters exceed the items stated below and at the same time the generator set should be stopped or delay stopping and fails to self start,Over voltage and low voltage,over frequency,over speed,low oil pressure,high temperature,low water level and over load. |