DIESEL GENERATOR SET | |||||||||
Genset Model | KH-1000GF | ||||||||
Prime Power | 1000KW/1250KVA | ||||||||
Standby Power | 1100KW/1375KVA | ||||||||
Rated Voltage (V) | 400 | ||||||||
Rated Current (A) | 1804 | ||||||||
Rated Frequency (Hz) | 50 | ||||||||
Rated Speed (RPM) | 1500 | ||||||||
Power Factor (COS¢) | 0.8 (lagging) | ||||||||
ENGINE DATA | |||||||||
Engine Brand | Perkins | ||||||||
Engine Model | 4012-46TWG2A | ||||||||
No. of Cylinders | 12 | ||||||||
Cylinder Arrangement | V | ||||||||
Cycle | 4 Stroke | ||||||||
Aspiration | Quad Turbocharged, Aftercooled | ||||||||
Fuel System | Unit Injection | ||||||||
Bore*Stroke (mm*mm) | 160*190 | ||||||||
Displacement (Liter) | 45.84 | ||||||||
Compression Ratio | 12.8:1 | ||||||||
Cooling System | Water-Cooled | ||||||||
Starting Method | DC 24V Electrical Starting | ||||||||
Lubricating Oil Capacity Sump Maximum (Litres) | 157.5 | ||||||||
Total Cooltant Capacity - Engine Only (Liter) | 73 | ||||||||
Fuel Consumption (g/kWh) | 100% | 196 | |||||||
75% | 196 | ||||||||
50% | 204 | ||||||||
ALTERNATOR DATA | |||||||||
Alternator Brand | Stamford | ||||||||
Alternator Model | PI734A | ||||||||
Connecting Type | 3 Phases and 4 Wires | ||||||||
Number of Bearing | Single | ||||||||
Production Grade | IP23 | ||||||||
Altitude | ≤ 1000m | ||||||||
Exciter Type | Brushless, Self-exciting, AVR & 100% Copper Winding Wire | ||||||||
Insulation Class | H | ||||||||
Telephone Influence Factor (TIF) | ≤ 50 | ||||||||
Telephone Harmonic Factor (THF) | ≤ 2% | ||||||||
Voltage Regulation, Steady State | 1.00% | ||||||||
Transient State Voltage | ≤ -15% ~ +20% |