DIESEL GENERATOR SET | ||||||||
Gensets Model | KH-300GF | |||||||
Prime Power | 300KW/375KVA | |||||||
Standby Power | 320KW/400KVA | |||||||
Rated Voltage(V) | 380/220 | |||||||
Rated Frequency(Hz) | 50 | |||||||
Rated Speed (RPM) | 1500 | |||||||
Power Factor(COS¢) | 0.8(lagging) | |||||||
Noise Level | 70dB in 7 meters | |||||||
ENGINE DATA | ||||||||
Engine brand | YUCHAI | |||||||
Engine model | YC6K500-D30 | |||||||
Configuration | Vertical, In-line, 6-Cylinder, Water cooled, Four stroke | |||||||
Aspiration | Tubocharged & Intercooled | |||||||
Bore×Stroke(mm) | 129*155 | |||||||
Displacement (L) | 12.16 | |||||||
Compression ratio | 14.5:1 | |||||||
Prime Power/Speed (kW/r/min) | 335/1500 | |||||||
Fuel consumption g/(kW·h) | ≤192 | |||||||
Total lubrication system capacity | 40L | |||||||
Oil capacity(L) | 32 | |||||||
Starting Method | DC 24V electrical starting | |||||||
ALTERNATOR DATA | ||||||||
Alternator brand | MARATHON | |||||||
Alternator model | MP-320-4A | |||||||
Number of Phase | 3 | |||||||
Connecting Type | 3 Phase and 4 Wires | |||||||
Number of Bearing | Single | |||||||
Protection Grade | IP22 | |||||||
Altitude | ≤1000m | |||||||
Exciter Type | Brushless, Self-exciting, AVR &100% Copper winding wire | |||||||
Insulation Class | H | |||||||
Telephone Influence Factor (TIF) | ≤50 | |||||||
Telephone Harmonic Factor(THF) | ≤2% | |||||||
Steady State Voltage Regulation | ±0.5%~±1.0% | |||||||
Transient State Voltage Regulation | ≤-15%~+20% |